AC Supply Voltage
200 - 600 VacHP Ratings
10 to 1125 HP
Amp Ratings
39 to 1250 AmpsOverload Rating
500% for 60 sec (1.15 SF)
Acceleration Adjustments Ramp types Voltage ramp or current ramp Starting torque 0 - 100% of line voltage or 0 - 600% of FLA Ramp time 1 to 120 seconds Current limit 200 - 600% |
Retentive Thermal Memory Remembers the thermal condition of the motor even in the event of a power brown-out or black-out. Extrapolates motor temperature using a real-time clock. |
Dual Ramp Settings* Four (4) programmable ramp options |
Dynamic Reset Capacity Overload will not reset until thermal capacity in the motor is sufficient for a successful restart. Starter learns and retains this information from previous starts. |
Deceleration Adjustments Begin decel level 0 - 100% of line voltage Stop level 0 to 1% less than begin decel Decel time 0 - 60 seconds Operation during overload Ramp down or coast-to-stop Jog Settings* Jog at set current 100 - 500% of FLA Jog at set voltage 0 - 100% of line voltage Voltage jog max time 0 - 20 seconds |
Phase Current Imbalance/Loss Protection Imbalance trip level 5 - 30% current between any two phases Imbalance trip delay 0 - 20 seconds Phase loss Trips on any phase current loss Electronic Shear Pin Protection Shear pin trip level 50 - 300% of motor FLA Shear pin trip delay 0 - 20 seconds
|
Kick Start Settings Kick start 0 - 100% of line voltage Kick start time 0.1 - 2 seconds Programmable Output Relays Three (3) relays can be individually programmed for change of state indication for any one of 18 conditions. Type / Rating FORM C (SPDT), rated 5 amps, 240VAC max (1200VA) |
Load Loss Trip Protection Under current trip level 10 - 90% of motor FLA Under current trip delay 0 - 20 seconds Coast Down (Back Spin) Lockout Timer Coast down time 0 - 60 minutes |
Start & Run Protection Two programmable overload trip curves allow for the thermal capacity required to start the load while providing motor overload protection needed during the run time. Start: Programmable for Class 5 - 30 Run: Programmable for Class 5 - 30, enabled when starter detects motor is "At-Speed" Reset: Manual or automatic, selectable via programming The XLD Series recognizes motor cool-down rates are a function of the run time and that sometimes a motor will cool faster if allowed to run. Real-Time Thermal Modeling Continuously calculates motor operating temperature even when your motor isn’t running. Knows when your motor is cool enough for a successful restart |
Starts-per-Hour Lockout Timer Starts-per-hour 1 - 10 successful starts per hour Time between starts 0 - 60 min. between start attempts Phase Rotation Phase sequence insensitive Shorted Load During start, injects voltage for ? second and will trip if it sees a current surge Short Circuit Trips in 12.5 ms at 10x unit current rating during run Shorted SCR Trips on a voltage drop of less than 1? V across any SCR pair Shunt Trip Relay trips on current flow while in the OFF mode (multiple shorted SCRs) Over Temperature Thermal sensors on heat sinks trip when temperature exceeds 185° F |